• 全部
  • 经验案例
  • 典型配置
  • 技术公告
  • FAQ
  • 漏洞说明
  • 全部
  • 全部
  • 大数据引擎
  • 知了引擎
产品线
搜索
取消
案例类型
发布者
是否解决
是否官方
时间
搜索引擎
匹配模式
高级搜索

【EVA】如何正确开关EVA 4000/4100/6000/6100/8000/8100

2021-04-20 发表
  • 0关注
  • 0收藏 1054浏览
粉丝:4人 关注:15人

问题描述

如何正确开关EVA 4000/4100/6000/6100/8000/8100


解决方法

1. Start HP P6000 Command View.
2. Select the appropriate storage system in the Navigation pane. The Initialized Storage System Properties window for the selected storage system opens.
3. Click Shut down. The Shutdown Options window opens.
4. Under System Shutdown click Power Down. If user want to delay the initiation of the shutdown, enter the number of minutes in the Shutdown delay field. The controllers complete an orderly shutdown and then power OFF. The disk enclosures then power OFF. Wait for the shutdown to complete.
5. Turn OFF the power to the rack power distribution units. Even though the disk enclosures are powered off in Step 4, unless the power on the rack distribution units are turned off, the I/O modules remain powered on in a standby state.
The shutdown process performs the following functions in the indicated order:
1. Flushes cache
2. Removes power from the controllers
3. Disables cache battery power
4. Removes power from the drive enclosures
5. Disconnects the system from HP P6000 Command View


Shutting down the storage system from the array controller:
1. Turn OFF the power switch on the rear of each HSV controller.
2. Turn OFF the circuit breakers on both of the EVA rack Power Distribution Units (PDU).
3. If management server is an SMA and you are not using it to manage other storage arrays, shut down the SMA. From the SMA user interface, click Settings, Maintenance, Shutdown.

Starting the storage system (Power On the array):
1. Verify that each fabric Fibre Channel switch to which the HSV controllers are connected is powered up and fully booted. The power indicator on each switch should be on.
If you must power up the SAN switches, wait for them to complete their power-on boot process before proceeding. This may take several minutes.
2. If the management server you shut down is an SMA, power it on and wait for it to completely boot. Verify the SMA is running by logging into it using the web interface.
NOTE: Before applying power to the rack, ensure that the power switch on each HSV controller is off.
3. Power on the circuit breakers on both EVA rack PDUs. Verify that all drive enclosures are operating properly. The status indicator and the power indicator should be ON (green).
4. Wait three minutes and then verify that all disk drives are ready. The drive ready indicator and the drive online indicator should be on (green).
5. Power on the upper controller. It takes the role of primary controller.
6. If you want the preferred path setting to be applied, wait three seconds and power on the lower controller. (Otherwise, wait 10 seconds before powering on the lower controller.) It takes the role of secondary controller.
7. Verify that the Operator Control Panel (OCP) display on each controller displays the storage system name and the EVA WWN.
8. Start HP P6000 Command View and verify connection to the storage system. If the storage system is not visible, click HSV Storage Network in the Navigation pane, and then click Discover in the Content pane to discover the array.
NOTE: If the storage system is still not visible, reboot the management server to re-establish the communication link.
9. Check the storage system status using HP P6000 Command View to ensure everything is operating properly. If any status indicator is not normal, check the log files or contact your HP-authorized service provider for assistance.

该案例对您是否有帮助:

您的评价:1

若您有关于案例的建议,请反馈:

作者在2021-11-13对此案例进行了修订
0 个评论

该案例暂时没有网友评论

编辑评论

举报

×

侵犯我的权益 >
对根叔知了社区有害的内容 >
辱骂、歧视、挑衅等(不友善)

侵犯我的权益

×

泄露了我的隐私 >
侵犯了我企业的权益 >
抄袭了我的内容 >
诽谤我 >
辱骂、歧视、挑衅等(不友善)
骚扰我

泄露了我的隐私

×

您好,当您发现根叔知了上有泄漏您隐私的内容时,您可以向根叔知了进行举报。 请您把以下内容通过邮件发送到pub.zhiliao@h3c.com 邮箱,我们会尽快处理。
  • 1. 您认为哪些内容泄露了您的隐私?(请在邮件中列出您举报的内容、链接地址,并给出简短的说明)
  • 2. 您是谁?(身份证明材料,可以是身份证或护照等证件)

侵犯了我企业的权益

×

您好,当您发现根叔知了上有关于您企业的造谣与诽谤、商业侵权等内容时,您可以向根叔知了进行举报。 请您把以下内容通过邮件发送到 pub.zhiliao@h3c.com 邮箱,我们会在审核后尽快给您答复。
  • 1. 您举报的内容是什么?(请在邮件中列出您举报的内容和链接地址)
  • 2. 您是谁?(身份证明材料,可以是身份证或护照等证件)
  • 3. 是哪家企业?(营业执照,单位登记证明等证件)
  • 4. 您与该企业的关系是?(您是企业法人或被授权人,需提供企业委托授权书)
我们认为知名企业应该坦然接受公众讨论,对于答案中不准确的部分,我们欢迎您以正式或非正式身份在根叔知了上进行澄清。

抄袭了我的内容

×

原文链接或出处

诽谤我

×

您好,当您发现根叔知了上有诽谤您的内容时,您可以向根叔知了进行举报。 请您把以下内容通过邮件发送到pub.zhiliao@h3c.com 邮箱,我们会尽快处理。
  • 1. 您举报的内容以及侵犯了您什么权益?(请在邮件中列出您举报的内容、链接地址,并给出简短的说明)
  • 2. 您是谁?(身份证明材料,可以是身份证或护照等证件)
我们认为知名企业应该坦然接受公众讨论,对于答案中不准确的部分,我们欢迎您以正式或非正式身份在根叔知了上进行澄清。

对根叔知了社区有害的内容

×

垃圾广告信息
色情、暴力、血腥等违反法律法规的内容
政治敏感
不规范转载 >
辱骂、歧视、挑衅等(不友善)
骚扰我
诱导投票

不规范转载

×

举报说明

提出建议

    +

亲~登录后才可以操作哦!

确定

亲~检测到您登陆的账号未在http://hclhub.h3c.com进行注册

注册后可访问此模块

跳转hclhub

你的邮箱还未认证,请认证邮箱或绑定手机后进行当前操作